Sample Report

Try It Yourself
SAMPLE REPORT

Harrington Home Inspections

(813) 555-0142

mike@harringtoninspections.com

Home Inspection Report
Subject Property:123 Sample Street, Anytown, US 00000
Prepared For:John & Jane Smith
Inspection Date:March 20, 2026
Property Type:Single Family
Year Built:1985
Square Footage:2,100 sq ft
Report #:INS-2026-0142
Inspector:Mike Harrington, License #HI-4821
This report was prepared for the sole use of the named client. It is not transferable. This report is not a substitute for any inspections or warranties required under any residential purchase contract.
SUMMARY OF MAJOR DEFECTS & RECOMMENDED IMPROVEMENTS

This summary does not supersede the full report. YOU MUST READ THE FULL REPORT for complete findings.

2
Safety Hazards
5
Repairs Recommended
3
Monitor Items
15
Total Observations
Repair / ReplaceRoof Covering: Three-tab asphalt shingles on the main roof exhibit significant granule loss and curling along the south-facing slope. Estimated age is 20 years, which exceeds the typical 15-20 year service life for this material. Multiple shingles near the chimney flashing are lifted and cracked.
Safety HazardGFCI Protection: Kitchen countertop receptacles within 6 feet of the sink lack Ground Fault Circuit Interrupter (GFCI) protection on both sides. This is a confirmed safety hazard.
Safety HazardService Panel: Main electrical panel is a Federal Pacific Electric (FPE) Stab-Lok panel. FPE Stab-Lok panels are a documented safety concern due to breakers that may fail to trip during overcurrent conditions, posing a fire hazard.
Repair / ReplaceSmoke & CO Detectors: Smoke detectors are missing from two second-floor bedrooms. Carbon monoxide detector present and functional near the gas furnace.
Repair / ReplaceKitchen Fixtures: Kitchen sink faucet exhibits a persistent drip at approximately 2 drops per second when in the off position. Garbage disposal unit is leaking from the bottom housing seal when running.
MonitorWater Heater: Gas water heater is approximately 16 years old, exceeding the typical 10-12 year service life. Visible rust at the base. TPR valve discharge pipe terminates 4 inches above the floor instead of within 6 inches of the floor as required.
MonitorFurnace: Unit is operational and producing heat. Air filter is severely clogged and does not appear to have been replaced in 6+ months. Reduced airflow can cause heat exchanger stress.
MonitorFoundation Walls: Horizontal crack observed approximately 15 feet in length, 1/8 inch in width. No visible displacement or active water intrusion at time of inspection. Horizontal cracks can indicate lateral pressure from soil.
Repair / ReplaceInsulation: Insulation measured at approximately 6 inches depth, providing estimated R-19 value. Current energy code for this climate zone requires R-38 minimum.
Repair / ReplaceVentilation: Bathroom exhaust fan duct terminates in the attic space instead of being vented to the building exterior. This introduces warm, moist air into the attic, promoting condensation and mold growth.
Roofing

Inspection performed from ground level and accessible areas only. No destructive testing performed.

Roof Covering

Material: 3-tab asphalt shingles

Location: South-facing slope, chimney area

INNINPD
Repair / Replace

Granule loss and curling on south-facing roof slope

Three-tab asphalt shingles on the main roof exhibit significant granule loss and curling along the south-facing slope. Estimated age is 20 years, which exceeds the typical 15-20 year service life for this material. Multiple shingles near the chimney flashing are lifted and cracked.

Recommend: Recommend evaluation by a qualified roofing contractor for full replacement. Continued deterioration will lead to water intrusion.
Gutters & Downspouts

Material: Aluminum

Location: Full perimeter

INNINPD
Inspected
Roof Flashing

Material: Aluminum step flashing

Location: Chimney and wall intersections

INNINPD
Inspected
Electrical System

Inspection limited to visible and accessible components. Concealed wiring not evaluated.

GFCI Protection

Location: Kitchen, both sides of sink

INNINPD
Safety Hazard

Non-GFCI outlet within 6 feet of kitchen sink

Kitchen countertop receptacles within 6 feet of the sink lack Ground Fault Circuit Interrupter (GFCI) protection on both sides. This is a confirmed safety hazard.

Recommend: ACTION REQUIRED — SAFETY HAZARD: Recommend immediate installation of GFCI-protected receptacles at all kitchen countertop locations by a qualified licensed electrician.
Service Panel

Material: Federal Pacific Electric (FPE) Stab-Lok, 150A

Location: Basement, east wall

INNINPD
Safety Hazard

Federal Pacific Stab-Lok panel label and breakers

Main electrical panel is a Federal Pacific Electric (FPE) Stab-Lok panel. FPE Stab-Lok panels are a documented safety concern due to breakers that may fail to trip during overcurrent conditions, posing a fire hazard.

Recommend: ACTION REQUIRED — SAFETY HAZARD: Recommend complete panel replacement by a qualified licensed electrician. This is a known defect with documented fire risk.
Smoke & CO Detectors

Location: Second floor bedrooms 2 and 3

INNINPD
Repair / Replace

Smoke detectors are missing from two second-floor bedrooms. Carbon monoxide detector present and functional near the gas furnace.

Recommend: Recommend installation of smoke detectors in all bedrooms and on each level of the home.
Branch Wiring & Receptacles

Material: Copper NM-B (Romex)

Location: Throughout

INNINPD
Inspected
Plumbing

Inspection limited to visible supply and drain lines. Concealed piping not evaluated.

Kitchen Fixtures

Location: Kitchen

INNINPD
Repair / Replace

Leaking garbage disposal housing seal

Kitchen sink faucet exhibits a persistent drip at approximately 2 drops per second when in the off position. Garbage disposal unit is leaking from the bottom housing seal when running.

Recommend: Recommend repair or replacement of the kitchen faucet cartridge and garbage disposal unit by a qualified licensed plumber.
Water Heater

Material: 2010 Rheem 40-gallon, gas

Location: Basement utility area

INNINPD
Monitor

Rust at base of 2010 Rheem water heater

Gas water heater is approximately 16 years old, exceeding the typical 10-12 year service life. Visible rust at the base. TPR valve discharge pipe terminates 4 inches above the floor instead of within 6 inches of the floor as required.

Recommend: Monitor for continued deterioration. Budget for replacement. Recommend correction of TPR discharge pipe termination by a qualified licensed plumber.
Supply & Drain Lines

Material: Copper supply, PVC drain

Location: Visible in basement

INNINPD
Inspected
HVAC

Heating system operated with normal controls. Cooling system not tested (exterior temperature below 60°F).

Furnace

Material: 2011 Carrier gas forced-air

Location: Basement mechanical room

INNINPD
Monitor

Severely clogged furnace air filter

Unit is operational and producing heat. Air filter is severely clogged and does not appear to have been replaced in 6+ months. Reduced airflow can cause heat exchanger stress.

Recommend: Replace air filter immediately. Monitor given age. Schedule annual HVAC maintenance with a qualified HVAC technician.
Structure / Foundation

Inspection limited to visible and accessible structural components.

Foundation Walls

Material: Poured concrete

Location: Basement, east wall

INNINPD
Monitor

Horizontal crack along east foundation wall

Horizontal crack observed approximately 15 feet in length, 1/8 inch in width. No visible displacement or active water intrusion at time of inspection. Horizontal cracks can indicate lateral pressure from soil.

Recommend: Monitor for changes in width or displacement over the next 6-12 months. If progression is observed, recommend evaluation by a qualified structural engineer.
Floor Structure

Material: 2x10 wood joists, 16" O.C.

Location: Basement ceiling / first floor

INNINPD
Inspected
Attic / Insulation

Attic accessed via pull-down stairs. Inspection limited to visible areas from access point.

Insulation

Material: Blown cellulose, ~6 inches (~R-19)

Location: Full attic space

INNINPD
Repair / Replace

Thin blown cellulose insulation in attic (~6 inches)

Insulation measured at approximately 6 inches depth, providing estimated R-19 value. Current energy code for this climate zone requires R-38 minimum.

Recommend: Recommend adding insulation to achieve minimum R-38 by a qualified insulation contractor.
Ventilation

Location: Attic, above main bathroom

INNINPD
Repair / Replace

Exhaust duct terminating in attic space

Bathroom exhaust fan duct terminates in the attic space instead of being vented to the building exterior. This introduces warm, moist air into the attic, promoting condensation and mold growth.

Recommend: Recommend extending the bathroom exhaust duct to terminate at the building exterior by a qualified contractor.
CLIENT GUIDE — Understanding Your Inspection Results

This section explains the inspection findings in plain language to help you make informed decisions about this property.

🔴 Items Requiring Immediate Attention
1. GFCI Protection — Kitchen

What We Found: The electrical outlets near your kitchen sink do not have Ground Fault Circuit Interrupter (GFCI) protection. GFCI outlets are the ones with the little "test" and "reset" buttons — they cut the power instantly if they detect a shock hazard.

What This Means: Without GFCI protection near water sources, there is a real risk of electrical shock. This is one of the most common safety issues found in older homes and is required by current electrical code.

What To Do: Have a licensed electrician install GFCI-protected outlets at all kitchen countertop locations. This is a straightforward repair.

Estimated Cost: $150 – $300

2. Electrical Panel — Federal Pacific Stab-Lok

What We Found: Your home has a Federal Pacific Electric (FPE) "Stab-Lok" breaker panel. These panels have a well-documented history of breakers failing to trip when they should.

What This Means: When a breaker does not trip during an overload, the wiring can overheat, which is a fire hazard. The Consumer Product Safety Commission has studied these panels extensively. This is not something to defer.

What To Do: Have a licensed electrician replace the entire panel with a modern one. This is the single most important item in this report.

Estimated Cost: $1,800 – $3,500

🟡 Items to Address Within 30 Days
1. Roof Covering

What We Found: The roof shingles on the south side are past their expected lifespan. They are losing their protective granules and several are cracking or curling.

What This Means: A roof in this condition will eventually leak. It may not be leaking today, but it does not have many years of life left. Waiting too long can lead to water damage inside the home that is far more expensive to fix.

What To Do: Get quotes from 2-3 roofing contractors for a full roof replacement. This can likely be planned over the next few months rather than done immediately.

Estimated Cost: $8,000 – $15,000

2. Smoke Detectors — Bedrooms

What We Found: Two upstairs bedrooms are missing smoke detectors entirely.

What This Means: Smoke detectors save lives. Current code requires one in every bedroom and on every level of the home.

What To Do: Install smoke detectors in the affected bedrooms. This is inexpensive and can be done yourself or by a handyman.

Estimated Cost: $30 – $80

3. Attic Insulation

What We Found: The attic has about 6 inches of blown insulation, providing roughly R-19. Current energy code for this area requires R-38.

What This Means: Insufficient insulation means higher heating and cooling bills and less comfort. You are essentially losing energy through the ceiling.

What To Do: Have an insulation contractor add blown insulation to bring the attic to R-38 or higher.

Estimated Cost: $1,500 – $3,000

4. Bathroom Exhaust — Venting Into Attic

What We Found: The bathroom exhaust fan duct dumps moist air directly into the attic instead of venting it outside.

What This Means: Hot, humid air from showers condenses on cold attic surfaces. Over time, this causes mold, wood rot, and can damage the roof structure from underneath.

What To Do: Extend the exhaust duct to terminate at the exterior of the building. A general contractor or HVAC tech can handle this.

Estimated Cost: $200 – $500

5. Kitchen Fixtures

What We Found: The kitchen faucet drips when turned off, and the garbage disposal is leaking from the bottom seal.

What This Means: A dripping faucet wastes water and a leaking disposal can damage the cabinet underneath over time.

What To Do: Have a plumber replace the faucet cartridge and the garbage disposal unit.

Estimated Cost: $250 – $500

🔵 Items to Monitor Over Time
1. Water Heater

What We Found: The gas water heater is 16 years old (typical lifespan is 10-12 years) and has rust forming at the base.

What This Means: It is working now, but it is well past its expected life. When water heaters fail, they can leak 40+ gallons of water. The discharge pipe for the safety valve also needs a minor correction.

What To Do: Budget for replacement in the near future. Have a plumber correct the TPR discharge pipe.

Estimated Cost: $1,200 – $2,000 (replacement)

2. Foundation Crack — East Wall

What We Found: There is a horizontal crack about 15 feet long in the basement wall. No water intrusion was observed at the time of inspection.

What This Means: Horizontal cracks can indicate soil pressure pushing on the wall. This one appears stable but should be watched for changes.

What To Do: Mark both ends of the crack with tape and the date. Check every 3 months. If it grows wider or you see displacement, consult a structural engineer.

Estimated Cost: $0 (monitoring) – $5,000+ (if repair needed)

3. Furnace

What We Found: The gas furnace is 15 years old and the air filter was severely clogged.

What This Means: A clogged filter restricts airflow and can stress the heat exchanger, shortening the life of the unit. The furnace is getting older but functional.

What To Do: Replace the filter immediately. Schedule annual HVAC maintenance. Budget for eventual replacement.

Estimated Cost: $20 (filter) – $4,000+ (replacement if needed)

This guide is provided for your convenience and does not replace the detailed findings in the full report above. All cost estimates are approximate ranges — obtain professional quotes before making decisions.

Harrington Home Inspections · CONFIDENTIAL123 Sample Street, Anytown, US 00000

This entire report was generated from voice notes in 90 seconds

No typing. No templates. No canned comments. Just speak naturally and let AI do the rest.